iTrans™

Stainless Steel

  • O2, toxic or combustible gas detector
  • Corrosion resistant housing
  • Dual sensor platform (on-board & remote placement)
  • 4-20 mA and ModBus RTU output

Product Information

Overview

Enclosed within an explosion-proof stainless steel housing, the Stainless Steel iTrans™ is built to withstand corrosion in harsh environments such as offshore drilling platforms, chemical plants or applications near a saltwater coastline.

The iTrans monitors employ an intelligent electronics platform to provide maximum flexibility, superior performance and lower installation costs. The three or four wire system allows gas sensors to be mounted on-board or remotely up to 200 meters away, and can accommodate more than 200 transmitters in RS485 bus configuration. Able to monitor any combination of gases for a specific environment, iTrans™ uses our industry-proven “smart” sensor technology and safety features including automatic sensor recognition, zero and cal fault protection, and access code security.

The microprocessor-controlled transmitters are capable of independent operation or multi-point system configuration and can transmit a 4-20mA signal or ModBus RTU digital output to any control device or PLC. With optional on-board relays, the monitor has the added ability of stand-alone operation, activating alarms, horns, or fans and can also shut down a system without the need to wire back to a central control panel.

iTrans also offers a relay deactivation feature to prevent accidental alarm activation during calibrations. The units also feature simple non-intrusive calibration, ultra-bright LED display, programmable alarms, and on-board sensor life indicators.

 

Specification

Technical Specifications

Enclosures:

Cast aluminum, poly-bonded coating or 316 stainless steel. Both are explosion-proof, NEMA 7X, IP66 rated

Sensors:

Combustible Gases: Catalytic bead and/or Non-Dispersive Infrared(NDIR) Oxygen / Toxic Gases: Electrochemical diffusion

Measuring Ranges:

Combustible gases: 0-100% LEL in 1% increments
Oxygen: 0-30% by volume in 0.1% increments
Ammonia: 0-200 ppm in 1 ppm increments
Carbon Monoxide: 0-999 ppm in 1 ppm increments
Hydrogen Sulfide: 0-500 ppm in 1 ppm increments
Sulfur Dioxide: 0.2-99.9 ppm in 0.1 ppm increments
Hydrogen Cyanide: 0.2-30 ppm in 0.1 ppm increments
Hydrogen Chloride: 0.2-30 ppm in 0.1 ppm increments
Phosphine: 0-1 ppm in 0.01 ppm increments
Nitrogen Dioxide: 0.2-99.9 ppm in 0.1 ppm increments
Nitric Oxide: 0-999 ppm in 1 ppm increments
Chlorine: 0.2-99.9 ppm in 0.1 ppm increments
Chlorine Dioxide: 0.02-1 ppm in 0.01 ppm increments
Hydrogen: 0-999 ppm in 1 ppm increments

Input Current (Max):

Toxic Gas / Oxygen: 150 mA at 24 VDC (single gas)
Combustible gases (Catalytic): 175 mA at 24 VDC, 0.6 A peak (single gas)
Combustible gases (Infrared): 150 mA at 24 VDC, 0.6 A peak (single gas)
Combined catalytic/infrared: 280 mA at 24 VDC (two gas)

Input Voltage:

12-28 VDC operating range (24 VDC typical)

Display:

Dual-channel split-screen LED display(4 digit,7-segment arrangement per channel) provides simultaneous display of one or two gases.

Signal Output:

4-20 mA, linear (analog) and ModBus RTU (digital)
RS485 digital communication with ModBus RTU software protocol system at 9600 baud. Three or four wire system capable of accommodating over 200 devices in bus configuration. Address selection through on-board 8-position dipswitch.

Alarm Relays:

3 alarm relays: Two user-programmable relays, SPST, N.O.; plus one fault relay, SPST, N.C.

Contact Capacity:

5 Amps at 30 VDC

Temperature Range:

-4°F to +122°F (-20°C to +50°C), typical

Humidity Range:

15-90% RH (non-condensing), typical

Approvals: (Sensor-specific)

Consult factory for current approval status
NRTL/c and CSA – Class I, Div. 1, 2, Groups B, C, D; AEx d IIB + H2
ATEX – Ex d IIB + H2 T5 (sensor-specific)
IEC – Ex d IIB + H2 T5 (sensor-specific)
China – GB 3836. 1-Ex d IIC T4; LEL version
GB15322-94 Fire protection

 

ATEX ZONE 1 OR 2
Gases: 
ClO2
CO
H2
H2S
HCl
CO/H2 null
HCN
NH3
NO
NO2
O2
PH3
SO2
  • Printer-friendly versionPrinter-friendly version

Product Types

  • Fixed Controllers
  • Fixed Transmitters
  • Fixed Accessories
  • Legacy Products
  • Product Policies

Share Your Success

See our full line of fixed gas detection products.

Share Your Success

Help us save more lives. Share your success with using Oldham fixed gas detection products and services.

You are here

Home

We’re here to help

Americas: +(1) 1-800-DETECTS
EMEA: +(33) 3 21 60 80 80
Asia-Pacific: +(86) 21 5899 3279

Feedback

Please take our Customer Satisfaction Survey.

The Industrial Scientific Family of Companies

Industrial Scientific: Portable Gas DetectorsOldham Gas: Fixed Gas DetectorsPredictive Solutions: Safety Software

Terms of Use | Privacy Statement

Copyright 2013 Oldham Gas. All Rights Reserved. Web site by Impactiv, Inc.