|
Enclosures:
|
Cast aluminum, poly-bonded coating or 316 stainless steel. Both are explosion-proof, NEMA 7X, IP66 rated
|
|
Sensors:
|
Combustible Gases: Catalytic bead and/or Non-Dispersive Infrared(NDIR) Oxygen / Toxic Gases: Electrochemical diffusion
|
|
Measuring Ranges:
|
Combustible gases: 0-100% LEL in 1% increments
Oxygen: 0-30% by volume in 0.1% increments
Ammonia: 0-200 ppm in 1 ppm increments
Carbon Monoxide: 0-999 ppm in 1 ppm increments
Hydrogen Sulfide: 0-500 ppm in 1 ppm increments
Sulfur Dioxide: 0.2-99.9 ppm in 0.1 ppm increments
Hydrogen Cyanide: 0.2-30 ppm in 0.1 ppm increments
Hydrogen Chloride: 0.2-30 ppm in 0.1 ppm increments
Phosphine: 0-1 ppm in 0.01 ppm increments
Nitrogen Dioxide: 0.2-99.9 ppm in 0.1 ppm increments
Nitric Oxide: 0-999 ppm in 1 ppm increments
Chlorine: 0.2-99.9 ppm in 0.1 ppm increments
Chlorine Dioxide: 0.02-1 ppm in 0.01 ppm increments
Hydrogen: 0-999 ppm in 1 ppm increments
|
|
Input Current (Max):
|
Toxic Gas / Oxygen: 150 mA at 24 VDC (single gas)
Combustible gases (Catalytic): 175 mA at 24 VDC, 0.6 A peak (single gas)
Combustible gases (Infrared): 150 mA at 24 VDC, 0.6 A peak (single gas)
Combined catalytic/infrared: 280 mA at 24 VDC (two gas)
|
|
Input Voltage:
|
12-28 VDC operating range (24 VDC typical)
|
|
Display:
|
Dual-channel split-screen LED display(4 digit,7-segment arrangement per channel) provides simultaneous display of one or two gases.
|
|
Signal Output:
|
4-20 mA, linear (analog) and ModBus RTU (digital)
RS485 digital communication with ModBus RTU software protocol system at 9600 baud. Three or four wire system capable of accommodating over 200 devices in bus configuration. Address selection through on-board 8-position dipswitch.
|
|
Alarm Relays:
|
3 alarm relays: Two user-programmable relays, SPST, N.O.; plus one fault relay, SPST, N.C.
|
|
Contact Capacity:
|
5 Amps at 30 VDC
|
|
Temperature Range:
|
-4°F to +122°F (-20°C to +50°C), typical
|
|
Humidity Range:
|
15-90% RH (non-condensing), typical
|
|
Approvals: (Sensor-specific)
|
Consult factory for current approval status
NRTL/c and CSA – Class I, Div. 1, 2, Groups B, C, D; AEx d IIB + H2
ATEX – Ex d IIB + H2 T5 (sensor-specific)
IEC – Ex d IIB + H2 T5 (sensor-specific)
China – GB 3836. 1-Ex d IIC T4; LEL version
GB15322-94 Fire protection
|